Deskripsi
The ACS580-01 is plug-in ready to control your compressors, conveyors, pumps, extruders, centrifuges, mixers, fans and many other variable and constant torque applications, in a variety of light industries, including food and beverage, plastic, textile, material handling, and agriculture. All essential features are built-in as standard, simplifying drive selection, and making additional hardware unnecessary. Versatile and straightforward settings menu and assistants enable fast setup, commissioning, use and maintenance, while rugged and robust design makes it a good fit for various environments. With the ACS580 drives you can easily take full control of your processes to comprehensively manage your plant. The wall-mounted ACS580-01 comes in IP21 enclosure as standard. Also, IP55 and flange mounting units are available.
| Cabinet-built drives, ACS580-07 (3-phase supply voltage range 380-480 V) | |||||||||||||
| Frame type | Frame size | 3-phase, UN = 400 V | 3-phase, UN = 480 V | ||||||||||
| Nominal ratings | Light-duty use | Heavy-duty use | Max. output current | Light-duty use | Heavy-duty use | Max. output current | |||||||
| PN | I N | I Ld | PLd | I Hd | PHd | Imax | I Ld | PLd | I Hd | PHd | Imax | ||
| (kW) | (A) | (A) | (kW) | (A) | (kW) | (A) | (A) | (hp) | (A) | (hp) | (A) | ||
| ACS580-07-0145A-4 | R6 | 75 | 145 | 138 | 75 | 105 | 55 | 178 | 124 | 100 | 96 | 75 | 178 |
| ACS580-07-0169A-4 | R7 | 90 | 169 | 161 | 90 | 145 | 75 | 247 | 156 | 125 | 124 | 100 | 247 |
| ACS580-07-0206A-4 | R7 | 110 | 206 | 196 | 110 | 169 | 90 | 287 | 180 | 150 | 156 | 125 | 287 |
| ACS580-07-0246A-4 | R8 | 132 | 246 | 234 | 132 | 206 | 110 | 350 | 240 | 200 | 180 | 150 | 350 |
| ACS580-07-0293A-4 | R8 | 160 | 293 | 278 | 160 | 246**) | 132 | 418 | 260 | 200 | 240 | 150 | 418 |
| ACS580-07-0363A-4 | R9 | 200 | 363 | 345 | 200 | 293 | 160 | 498 | 361 | 300 | 302 | 250 | 542 |
| ACS580-07-0430A-4 | R9 | 250 | 430 | 400 | 200 | 363***) | 200 | 617 | 414 | 350 | 361 | 300 | 542 |
| ACS580-07-0505A-4 | R10 | 250 | 505 | 485 | 250 | 361 | 200 | 560 | 483 | 400 | 361 | 300 | 560 |
| ACS580-07-0585A-4 | R10 | 315 | 585 | 575 | 315 | 429 | 250 | 730 | 573 | 450 | 414 | 350 | 730 |
| ACS580-07-0650A-4 | R10 | 355 | 650 | 634 | 355 | 477 | 250 | 730 | 623 | 500 | 477 | 400 | 730 |
| ACS580-07-0725A-4 | R11 | 400 | 725 | 715 | 400 | 566 | 315 | 1020 | 705 | 600 | 566 | 450 | 850 |
| ACS580-07-0820A-4 | R11 | 450 | 820 | 810 | 450 | 625 | 355 | 1020 | 807 | 700 | 625 | 500 | 1020 |
| ACS580-07-0880A-4 | R11 | 500 | 880 | 865 | 500 | 725*) | 400 | 1100 | 807 | 700 | 625 | 500 | 1020 |
| Cabinet-built drives, ACS580-01 , 3-phase, UN = 230 V (range 200 to 240 V). The power ratings are valid at nominal voltage 230 V (0.75 to 75 kW) | ||||||||
| Drive type | Frame size | |||||||
| Nominal ratings | Light-duty use | Heavy-duty use | Max. output current | |||||
| I N | PN | I Ld | PLd | I Hd | PHd | IMax | ||
| (A) | (kW) | (A) | (kW) | (A) | (kW) | (A) | ||
| ACS580-01-04A7-2 | R1 | 4.7 | 0.75 | 4.6 | 0.75 | 3.5 | 0.55 | 6.3 |
| ACS580-01-06A7-2 | R1 | 6.7 | 1.1 | 6.6 | 1.1 | 4.6 | 0.75 | 8.9 |
| ACS580-01-07A6-2 | R1 | 7.6 | 1.5 | 7.5 | 1.5 | 6.6 | 1.1 | 11.9 |
| ACS580-01-012A-2 | R1 | 12 | 3 | 11.8 | 3 | 7.5 | 2.2 | 19.1 |
| ACS580-01-018A-2 | R1 | 16.9 | 4 | 16.7 | 4 | 10.6 | 3 | 22 |
| ACS580-01-025A-2 | R2 | 24.5 | 5.5 | 24.2 | 5.5 | 16.7 | 4 | 32.7 |
| ACS580-01-032A-2 | R2 | 31.2 | 7.5 | 30.8 | 7.5 | 24.2 | 5.5 | 43.6 |
| ACS580-01-047A-2 | R3 | 46.7 | 11 | 46.2 | 11 | 30.8 | 7.5 | 62.4 |
| ACS580-01-060A-2 | R3 | 60 | 15 | 59.4 | 15 | 46.2 | 11 | 83.2 |
| ACS580-01-089A-2 | R5 | 89 | 22 | 88 | 22 | 74.8 | 18.5 | 135 |
| ACS580-01-115A-2 | R5 | 115 | 30 | 114 | 30 | 88 | 22 | 158 |
| ACS580-01-144A-2 | R6 | 144 | 37 | 143 | 37 | 114 | 30 | 205 |
| ACS580-01-171A-2 | R7 | 171 | 45 | 169 | 45 | 143 | 37 | 257 |
| ACS580-01-213A-2 | R7 | 213 | 55 | 211 | 55 | 169 | 45 | 304 |
| ACS580-01-276A-2 | R8 | 276 | 75 | 273 | 75 | 211 | 55 | 380 |
Nominal ratings
I N : Rated current available continuously without overloadability at 40 °C.
PN : Typical motor power in no-overload use.
Maximum output current Maximum output current
Imax : Maximum output current. Available for 2 seconds at start, then as long as allowed by drive temperature.
Light-overload use
I Ld : Continuous current allowing 110% I Ld for 1 minute every 10 minutes at 40 °C.
PLd : Typical motor power in light-overload use
The ratings apply for the frames R1 to R9 up to +40 °C in enclosed IP21/IP55. The ratings apply for the frames R1 to R9 up to +40 °C in enclosed IP21/IP55.
For derating at high altitudes, temperatures or switching frequencies, see the user’s HW manual, document code: 3AXD50000035866. For derating at high altitudes, temperatures or switching frequencies, see the user’s HW manual, document code: 3AXD50000035866.